42 Important Product Information
GFK-1671P
Open Issues and Problems
ID Description
CR73856
VersaPro 2.0x Imports Additional Variables from Control.
Details: When importing a Control folder into VersaPro, duplicate variables will be added in
the VDT. The “correct” variable in Control was assigned a type word, a length of 50 with 50
stored decimal values in %AI memory. VersaPro successfully imported these variables but
also added numerous variables with names equal to a memory address (ex: %AI0002) and
assigned it a stored value of one word length that corresponded to the stored value of the
“correct” variable at that specific address. If the stored value of the “correct” variable at that
specific location was 0, VersaPro did not add a variable.
Resolution: When importing Control folders, VersaPro will create variables in the following
order:
1) Create variables using the reference address as the name for references used in Logic based
on the operand type.
2) Create variables using the reference address as the name for references that have stored
values. Note variables will not be created if the store value is 0 because VersaPro treats a
stored value of 0 as meaning the reference has no stored value).
3) Create variables using the snf file.
This process may result in creating more variables than in the original Control folder. In order
to delete unused variables in Logic, the customer can use the Folder®Find Unused Variables
command to highlight the unused variables and then delete out any variables not needed for the
application. When deleting variables, the user should be careful not to delete variables that are
needed for other applications such as EGD which may not be referenced in Logic.
CR75496
Issues on Import of EGD configuration from Control folders.
Details: When importing a Control folder created with Version 2.3 that contains Ethernet
Global data, you may receive the following error:
“Import of Ethernet Global Data will be aborted. See following errors in Log File for details”.
The VersaPro information window will not give details about the issue. The hardware
configuration will be imported but without EGD data.
Resolution: In these cases the Control folder contains configuration parameters that are not
supported by VersaPro. To get details on what parameters are causing the problem, you
should open the Control folder within the VersaPro hardware configuration application. The
errors found will be presented in the hardware configuration log window. Based on these
errors, you will need to remove configuration items from your Control folder before importing.
CR75520
Retentive state conflicts after importing Logicmaster folder
Details: If your Logicmaster folder contains references used on word type of instructions and
also used as a bit on a contact or coil, you may receive retentive state conflicts because
VersaPro will default the word variable as retentive and the reference on the contact or coil
may be set as non-retentive.
Resolution: To avoid this warning, you should change the retentive states of the two variables
(the word and bit types) so that they match.