22 Important Product Information
GFK-1671P
Miscellaneous issues resolved:
24270
VersaPro online cross-reference and Use table reports do not specify the scope of the
report
Details: The Online Cross Reference and Usage table do not specify the blocks for which the
report is being generated
Resolution: The scope of the report is mentioned at the end of the report to indicate whether
the report is generated for the entire folder or specific blocks.
CR71758
Load to a new folder Not Equal.
Details: When a program, containing a variable declared as a bit in the VDT and used as a
word in the program is loaded from PLC into a new folder, the logic does not show equal.
Resolution: This is fixed in VersaPro 2.03 and the folder loads correctly.
22167
Loading a 90-70 CPU772 with GBC configured results in an error
Details: Load Hardware configuration from a 90-70 CPU772 having Genius Bus controller
configured. An internal program error message is displayed.
Resolution: This problem is resolved in VersaPro 2.03 and load works correctly.
Importing a LM90 folder may result in differences in retentiveness of references
Details: After importing a LM90 folder, you may see differences in the retentiveness of
references compared to the original Logicmaster folder. This can happen if you used bit
references (%I, %Q, %M) as input or output operands for a function and the bit reference is
on a byte boundary (1,9,17 etc).
Resolution: This is resolved in VersaPro 2.03 and folder imports correctly without any
difference in the retentiveness
21710
VersaPro does not take negative values in the parameters for 90-70 CALL function of a
C block
Details: VersaPro does not accept negative constant values in 90-70 CALL function of a C
block. On compilation, “Constant value out of range” is reported.
Resolution: VersaPro 2.03 accepts constant values in the range -32768 to 32767.