Important Product Information 27
GFK-1671P
Communication issues resolved:
ID Description
17024
Error when storing to UDR001 VersaMax Micro
Details: When a folder is stored to UDR001 in VersaPro 2.00, a store error “store error
0x6D09 -Unknown Target com error” is displayed.
CR75970
Loading into a folder in which the retentive state of some variables have been changed
from retentive to non-retentive.
Details: If you store a folder from VersaPro 2.00 to the PLC, change one or more variables
from retentive to non-retentive and then load from the PLC, your folder will remain unequal
because VersaPro will not update the retentive state of any variables that are retentive in the
PLC.
19302
VersaPro 2.00 cannot connect to fault table via ethernet
Details: When attempting to connect to Fault Table using VersaPro 2.00, an error message
saying “Requested server not found. Port is not configured” is displayed.
Resolution: The problem is the TCP communication drivers not being registered properly and
this has been corrected in release 2.01.
Hardware Configuration issues resolved:
ID Description
CR75620
Pulse Train with Ramp is not supported in VersaMax Micro.
Details: Pulse Train with Ramp is not a supported option for Channel Function parameter in
VersaMax Micro configuration.
Resolution: This option is no longer available in VersaPro 2.01.
16785
VersaPro crashes when the sweep mode is changed in 90-70 configuration
Details: When the sweep mode in the scan tab of CPX928 or CPX935 configuration is
changed from Normal to Constant Sweep or Constant Window, HWC application crashes with
the following error:
The instruction at "0x002a07a1" referenced memory at "0x00000148". The memory could not
be "read". Click OK to terminate the application.
16786
BKW Status bit is not set in ALG392 configuration
Details: Broken Wire (BKW) Status bit is not with an open-wire situation in ALG392
configuration.
16789
Data Area deletion problem in Profibus Master module
Details: In the Data Area tab of Profibus Master module (HE693PBM101), when one row is
deleted using Parameter->Delete, it also changes the Module # and Input/Output offsets of the
next data areas.
16790
Problem when storing a VersaMax CPU001 configuration with non-default memory
references.
Details: While attempting to store an existing folder with configurable memory (%AI, %AQ
and %R reference addresses with non-default values) to a CPU 001, a message box in
VersaPro 2.0 is displayed and the store fails. The message box error was "Store Error 0x05F4 -
Invalid Input Parameter in Request"
16833
Incorrect calculation of power consumption in Hardware configuration
Details: The power consumption values for several 90-30, 90-70 and VersaMax modules are
incorrect.
Resolution: The power consumption algorithm and values are corrected in VersaPro 2.01 for
all 90-30, 90-70 and VersaMax modules.